Regulation valve leakage standard

Source: Internet Release Date: 2012/3/8

Control valveLeakage standard
National standard GB/T4213.92

Leakage level Test medium test pressure Maximum seat leakage 1/h
I Determined by users and manufacturers
Water, air or nitrogen A 5×10-3× valve rated capacity
10-3×rated capacity of valve
Wed A or B 10-4×rated capacity of valve
Air or nitrogen A
Ⅳ-S1 Wed A or B 5×10-4× valve rated capacity
Air or nitrogen A
Ⅳ-S2 Air or nitrogen A 2×10-4×△P×D
V Wed B 1.8×10-7×△P×D
VI Air or nitrogen A 3×10-3×△P(Continued table of leakage)

续表

Valve seat diameter 20 25 40 50 65 80 100 150 200 250 300 350 400
Leakage ml / min 0.1 0.15 0.3 0.45 0.6 0.9 1.7 4.0 6.75 11.1 16.0 21.6 28.4
Number of bubbles/min 1 2 3 4 6 11 27 45

注:1.每分钟气泡数是用外径6mm、壁厚1mm的管子垂直浸入水下5~10mm深度的条件下测得的,管端表面应光滑。
2. If the valve seat diameter differs from one of the table values ​​by more than 2mm, the leakage coefficient can be obtained by interpolation, assuming that the leakage is proportional to the square of the valve seat diameter.
American Standard ANSI B16.104-197

Leakage level Maximum allowable leakage Test medium test pressure
0.5%Cv 10~52℃ air or water    
Maximum working pressure difference △P or 501b/in2 pressure difference, whichever is lower
0.1%Cv 10~52℃ air or water     
Maximum working pressure difference △P or 501b/in2 pressure difference, whichever is lower
0.01%Cv 10~52℃ air or water     
Maximum working pressure difference △P or 501b/in2 pressure difference, whichever is lower
V At nominal diameter per inch and 2 pressure difference per pound/inch,
Allow 0.0005ml/min of water leakage
10~52℃ water    
Maximum working pressure △P
Valve nominal diameter ml / min Number of bubbles/min 10~52℃ air or nitrogen     
Maximum working pressure difference △P or 501b/in2 pressure difference, whichever is lower
in mm
1 25 0.15 1
1.5 38 0.30 2
2 51 0.45 3
2.5 64 0.60 4
3 76 0.90 6
4 102 1.70 11
6 152 4.00 27
8 203 6.75 45
E-mial:[email protected]
Address: Desheng Road, Yongjia County, Zhejiang Province